Daikin FXDQ25PVET [304/394] Pc board defect

Daikin FXDQ32PVE [304/394] Pc board defect
Si34-704 Troubleshooting (OP: Central Remote Controller)
Troubleshooting 293
4. Troubleshooting (OP: Central Remote Controller)
4.1
M1
PC Board Defect
Remote
Controller
Display
M1
Applicable
Models
Central remote controller Intelligent Touch Controller
Schedule timer
Method of
Malfunction
Detection
Detect an abnormality in the DIII-NET polarity circuit.
Malfunction
Decision
Conditions
When + polarity and - polarity are detected at the same time.
Supposed
Causes
Defect of central remote controller PC board
Defect of Intelligent Touch Controller PC board
Defect of Schedule timer PC board
Troubleshooting Replace the central remote controller.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is the M1 displayed again?
Replace the central
equipment.
Central equipment: Normal
It is supposed that the
malfunction results from
external factors (e.g. noises)
from other equipment.
With M1 displayed
Turn ON the power supply of
the central equipment
with M1 displayed once again.
Without M1 displayed