Daikin FXDQ25PVET [243/394] Outdoor unit abnormal outdoor fan motor signal

Daikin FXDQ20PVET [243/394] Outdoor unit abnormal outdoor fan motor signal
Troubleshooting by Indication on the Remote Controller Si34-704
232 Troubleshooting
3.23
H7
Outdoor Unit: Abnormal Outdoor Fan Motor Signal
Remote
Controller
Display
H7
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Detection of abnormal signal from fan motor.
Malfunction
Decision
Conditions
In case of detection of abnormal signal at starting fan motor.
Supposed
Causes
Abnormal fan motor signal (circuit malfunction)
Broken, short or disconnection connector of fan motor connection cable
Fan Inverter PC board malfunction (A4P, A8P)