Daikin FXDQ25PVET [261/394] Outdoor unit momentary overcurrent of inverter compressor

Daikin FXDQ20PVET [261/394] Outdoor unit momentary overcurrent of inverter compressor
Troubleshooting by Indication on the Remote Controller Si34-704
250 Troubleshooting
3.35
L5
Outdoor Unit: Momentary Overcurrent of Inverter
Compressor
Remote
Controller
Display
L5
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Malfunction is detected from current flowing in the power transistor.
Malfunction
Decision
Conditions
When an excessive current flows in the power transistor.
(Instantaneous overcurrent also causes activation.)
Supposed
Causes
Defect of compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defect of inverter PC board