Daikin FXDQ25PVET [264/394] Troubleshooting output current check

Daikin FXDQ20PVET [264/394] Troubleshooting output current check
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 253
Troubleshooting Output current check
NO
NO
NO
YES
YES
NO
NO
NO
YES
Power OFF
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Check if the
stop valve is open.
Check if the
compressor lead wires are
normal.
Check if the
wiring and connection to
the compressor are
normal.
Insulation
resistance of the compressor
is 100 k or
below.
Compressor coils are
disconnected.
Connect the compressor lead
wires then restart the operation.
Check 4
Check if the power transistor
is normal.
Malfunction code
“L8” is displayed again.
Check if the
pressure difference between high
pressure and low pressure before
restarting is 0.2MPa
or below.
YES
YES
Open the stop valve.
Replace compressor
lead wires.
Correct the wiring and
connection.
Replace the inverter
compressor.
Replace the inverter
compressor.
Replace the inverter
PCB (A3P).
Continue operation.
Defective pressure
equalizing in the
refrigerant circuit.
Inspection of the
compressor.
Check 4
: Referring to the information on page 306.