Daikin FXDQ25PVET [163/394] Outdoor air processing unit field setting remote controller

Daikin FXDQ20PVET [163/394] Outdoor air processing unit field setting remote controller
Field Setting Si34-704
152 Test Operation
Setting of Air Flow Direction Adjustment Range
Make the following air flow direction setting according to the respective purpose.
Setting Table
Air flow rate switching at discharge grille for field air flow rate switching
When the optional parts (high performance filter, etc.) is installed, sets to change fan speed for
securing air flow rate.
Follow the instruction manual for the optional parts to enter the setting numbers.
Setting of the static pressure selection (for FXDQ model)
3.1.7 Outdoor Air Processing Unit-Field Setting (Remote Controller)
Note) Bold face in indicates the default setting.
Mode No. First Code No. Second Code No. Setting
13 (23) 4
01
Upward (Draft
prevention)
02 Standard
03
Downward (Ceiling
soiling prevention)
Model No. First Code No. Second Code No. External static pressure
13 (23) 5
01 Standard (15Pa)
02
High static pressure (44Pa)
Mode
No.
Setting
SW
No.
Setting
contents
Setting position No.
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
10
(20)
0 Stain of filter2500hr 1250hr —————————————
3
Filtering
time
cumulation
Display
No
display
—————————————
12
(22)
1
External
ON/OFF
input
Forced
stop
ON-OFF
control
—————————————
5
Power
failure
automatic
reset
Not
equipped
Equipped—————————————
14
(24)
3
Discharge
temperature
(cooling)
13°C 14 15 16 17 18 19 20 21 22 23 24 25 25 25
4
Discharge
temperature
(heating)
18°C 19 20 21 22 23 24 25 26 27 28 29 30 30 30