Daikin FXDQ25PVET [240/394] F3 outdoor unit abnormal discharge pipe temperature

Daikin FXDQ20PVET [240/394] F3 outdoor unit abnormal discharge pipe temperature
Si34-704 Troubleshooting by Indication on the Remote Controller
Troubleshooting 229
3.21 F3 Outdoor Unit: Abnormal Discharge Pipe
Temperature
Remote
Controller
Display
F3
Applicable
Models
RXQ5P~54P
Method of
Malfunction
Detection
Abnormality is detected according to the temperature detected by the discharge pipe
temperature sensor.
Malfunction
Decision
Conditions
When the discharge pipe temperature rises to an abnormally high level (135 degrees and
above)
When the discharge pipe temperature rises suddenly (120 degrees and above for 10
successive minutes)
Supposed
Causes
Faulty discharge pipe temperature sensor
Faulty connection of discharge pipe temperature sensor
Faulty outdoor unit PC board