Daikin FXDQ25PVET [219/394] Troubleshooting

Daikin RXQ16PHY1 [219/394] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si34-704
208 Troubleshooting
Troubleshooting
NO
Electronic
expansion valve
is connected to X7A
of indoor unit
PCB.
Coil check
(1) of electronic
expansion valve drive
indicates
normal.
NO
NO
YES
Relay
cables short circuit or
disconnected.
YES
Shut the power supply off after
connection and then restart.
Replace coil of electronic
expansion valve.
Replace relay cables.
When restarting the operation
after shutting the power supply off
does not work, replace indoor unit
PCB.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
YES
1: How to check the coil of electronic expansion valve drive
Remove the connector for electronic expansion valve (X7A) from PCB. Measure the resistance value
between pins and check the continuity to judge the condition.
1) White
2) Yellow
3) Orange
4) Blue
6) Brown
5) Red
The normal products will show the following conditions:
No continuity between (1) and (2)
Resistance value between (1) and (3) is approx. 300
Resistance value between (1) and (5) is approx. 150
Resistance value between (2) and (4) is approx. 300
Resistance value between (2) and (6) is approx. 150
White (1)
Red (5)
Orange (3)
φ1
φ3
Yellow
(2)
Brown
(6)
Blue
(4)
φ2 φ4
M