Daikin FXDQ25PVET [267/394] Troubleshooting

Daikin RXQ42PHY1 [267/394] Troubleshooting
Troubleshooting by Indication on the Remote Controller Si34-704
256 Troubleshooting
Troubleshooting
Continued from the previous page.
(Start failure due to aged operation.)
Liquid
refrigerant is accumulated in
compressor ( The unit is out of power
supply for more than
6 hours.)
Check if the
insulation resistance of the
compressor is 100k
or over.
Disconnection inside
the compressor
Cancel the liquid refrigerant
accumulation state.
(Leave the power supply on for
more than 6 hours.)
Replace the inverter compressor.
Replace the inverter compressor.
Replace the compressor inverter
PCB (A3P).
Recheck the compressor/
refrigerant circuit.
NO
NO
NO
YES
NO
YES
YES
YES
Check 4
Check if the power
transistor is
normal.
Check 4
: Referring to the information on page 306.