Daikin FXDQ25PVET [309/394] Troubleshooting op unified on off controller

Daikin FXDQ20PVET [309/394] Troubleshooting op unified on off controller
Troubleshooting (OP: Unified ON/OFF Controller) Si34-704
298 Troubleshooting
5. Troubleshooting (OP: Unified ON/OFF Controller)
5.1 Operation Lamp Blinks
Remote
Controller
Display
Operation lamp blinks
Applicable
Models
All model of indoor units
Unified ON/OFF controller
Method of
Malfunction
Detection
Detect the malfunction according to DIII-NET transmission data.
Malfunction
Decision
Conditions
Supposed
Causes
Malfunction of transmission between optional central controller and indoor unit
Connector for setting master controller is disconnected
Defect of unified ON/OFF controller PC board
Defect of indoor unit PC board
Malfunction of air conditioner