Field Setting Si34-704
166 Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory set
24
ENECUT test
operation (Domestic
Japan only)
8788777
ENECUT output OFF
8777778
ENECUT output forced ON
8777787
25 Low noise setting
8788778
Level 1 (outdoor fan with 6 step or lower)
8777778
Level 2 (outdoor fan with 5 step or lower)
8777787
Level 3 (outdoor fan with 4 step or lower)
8777877
26
Night-time low noise
operation start
setting
8788787
About 20:00
8777778
About 22:00 (factory setting)
8777787
About 24:00
8777877
27
Night-time low noise
operation end
setting
8788788
About 6:00
8777778
About 7:00
8777787
About 8:00 (factory setting)
8777877
28
Power transistor
check mode
8788877
OFF
8777778
ON
8777787
29
Capacity
precedence setting
8788878
OFF
8777778
ON
8777787
30 Demand setting 1
8788887
60 % demand
8777778
70 % demand
8777787
80 % demand
8777877
32
Normal demand
setting
8877777
OFF
8777778
ON
8777787
35
Setting of difference
in elevation for the
outdoor unit
8877788
Normal
8777777
65 m or less
8777887
90 m or less
8777888
38
Emergency
operation
(Master unit with
multi-outdoor-unit
system is inhibited to
operate.)
8877887
OFF
8777778
Master unit operation: Inhibited
8777787
39
Emergency
operation
(Slave unit 1 with
multi-outdoor-unit
system is inhibited to
operate.)
8877888
OFF
8777778
Slave unit 1 operation: Inhibited
8777787
40
Emergency
operation
(Slave unit 2 with
multi-outdoor-unit
system is inhibited to
operate.)
8878777
OFF
8777778
Slave unit 2 operation: Inhibited
8777787
42
Emergency
operation
(prohibition of INV
compressor
operation)
8878787
Normal operation
8777778
Emergency operation
(prohibition of INV compressor
operation)
8777787