Daikin FTXD50JV1B [96/164] Outdoor units

Daikin FTXD50JV1B [96/164] Outdoor units
Troubleshooting SiBE04-101
88 Service Diagnosis
4.2 Outdoor Units
4: ON, 1: OFF, 5: Blinks
Green: Flashes when in normal condition
Red: OFF in normal condition
- : Not used for troubleshooting
: Varies depending on the cases.
Note: 1. When a sensor error occurs, check the remote controller display to determine which sensor is
malfunctioning.
If the remote controller does not indicate the error type, conduct the following operation.
*Turn the power switch off and back on again. If the same LED indication appears again immediately
after the power is turned on, the fault is in the thermistor.
*If the above condition does not result, the fault is in the CT.
2. The indoor unit error indication may take the precedence in the remote controller display.
Outdoor Unit LED Indication Indication on the
remote controller
Description of the Fault Details of Fault
(Refer to the
indicated
page.)
Green Red
A1234
53333
Outdoor unit in normal condition
(Conduct a diagnosis of the indoor unit.)
54344A5
Operation halt due to cooling high pressure control 100
54343E5
Stoppage by OL actuation/Melt-down by temperature fuse 102
53443E6
Operation halt due to compressor seizing. 104
54444E7
DC fan motor seizing 105
53434 or E8
Operation halt due to detection of input overcurrent. 106
54343F3
Abnormal discharge pipe temperature. 101
54433H6
Operation halt due to faulty position detection sensor. 108
54433H8
Operation halt due to detection of CT abnormality. 109
54433H9
Operation halt due to outside air thermistor abnormality. 112
53343L5
Operation halt due to detection of output overcurrent. 110
54433J3
Operation halt due to discharge pipe thermistor abnormality, or
due to detection of disconnected discharge pipe thermistor.
112
54433J6
Operation halt due to outdoor unit heat exchanger thermistor
abnormality.
112
53344U0
Operation halt due to detection of insufficient gas. 113
54334U2
Stoppage by low voltage of the main circuit (LVP) 115
54344
Operation halt due to peak cut, freeze protection function or
indoor unit icing protection.
(Conduct a
diagnosis of the
indoor unit.)
4
————
Faulty outdoor unit PCB 116
3
————
Faulty outdoor unit PCB or signal transmitting/receiving circuit. 117