uPC3 rel 1.8 11/2021
15
- LS iC5
- LS iG5
- ABB ACS
- EC
- DFI
ATTENTION! For the underlined type of VFD it is
needed to input the required parameters by VFD
keyboard. There is no possibility to configure by uPC3.
Depending on the configuration selected, it is possible
to manually change the modbus address of individual
motors for supply and return for maximum 10 fans.
HMI Advanced Menu Unit cfg. ► I41
LS VFD (iC5 and iG5A)
For iC5
Parameter
Code
Value
Comment
Way of Control
DRV
3
Frequency setting
metod
Frq
8
Converter's
address in Modbus
Network
I60
-
Motor modbus
address
Reaction on
communication
time-out
I62
2
Stop
Communication
time-out
I63
30
30 sec.
For iG5
Parameter
Code
Value
Comment
Way of Control
DRV
3
Frequency setting
metod
Frq
7
Converter's
address in Modbus
Network
I60
-
Motor modbus
address
Reaction on
communication
time-out
I62
2
Stop
VTS EC motor
All necessary information in DTR for EC motor.
Additional information.
Procedure how to configure the rotary wheel:
- go to the motor mask Menu ► Unit cfg. I03, chose
"Rotor VFD type" as EC.
- After that there will new mask " I15" appear below,
enter this line
- You'll see the mask "old address: 4, new address: 4"
- There is "Set" option, choose "YES"
- The procedure of setting the fan will be carried out.
Once it is successfully finished you'll see the sign "test
mode". Note that during setting procedure the other
modbus members might give errors, but this is all right.
- Change "Set" option to "NO"
- After the whole procedure restart the controller
Pressure / Humidity / CO2 sensor
HMI Advanced Menu ► In/Out settings ► G03
Screen on which pressure / humidity / CO2
transducers can be activated. In addition, we can
choose the type of pressure transducer on the G04
screen