VTS Ventus VVS300 [27/47] Regulation

VTS American VENTUS AVS 085 [27/47] Regulation
uPC3 rel 1.8 11/2021
27
Change of set point is at following screens Sa06
and Sa07 you set the percentage of 0-100% in
reference to the value set in parameters.
For example: 60% - means 60% of nominal airflow.
6.10 Mixing chamber control
Acccording to CO2 value, if present, a PID will
calculate the request for the mixing chamber.
If the PID is higher, then the mixing chamber will
close more and more.
The greater request between CO2 request and
freecooling/freeheating, will actuate the damper.
The mixing chamber can be setup from service in
the following ways to bypass the request by
freecooling and CO2 in the following ways:
Disabled: the mixing chamber is always closed
and the recovery is always active.
Enabled at startup: at startup there could be a fast
heating option to by pass the external condition for
a while and allows the devices to warm up quickly.
Enabled by request: by request from HMI
Advanced is possible to enable the mixing damper
until the temperature conditions reach the setpoint.
6.11 CO
2
Regulation
A signal is split and has a direct impact on the
degree of participation of outside air and provides
a correction signal to drive the VFD. VFD correction
signal is limited to the MAX allowable adjustments.
6.12 Minor functions
Antistuck procedure
In case of pumps or steam configured, the SW
must check if the pumps stayed OFF for a long
time. After one week of pump off, it has to start in
any condition to avoid the risk of stack. The valve
will open at 100%. Time is not saved in permanent
memory.
Fire alarm
In case of fire alarm by digital input or in case of
exhaust temperature > 70°C, the fire alarm
procedure is activated.
All the devices are stop, but the fan can run
according to service parameter.
Filter alarm
When the dirty filter alarm is active, it is possible to
increment the fans speed of a settable %.
Forcing I/O
It’s possible to force the input values and the
outputs values in In/Out settings menu.
Scheduler
On the HMI Basic it is possible to set the number
of enabled bands (maximum 6), for each one the
starting time and the setpoint of the room
temperature.
Both for uPC3 scheduler and HMI Basic it will be
possible to apply the time bands set to all the days
of the week, Monday to Friday, Saturday and
Sunday, day by day.
On the uPC3 there will be 4 time bands and for
each one it will be possible to set the starting time
and the unit status (Off, Economy, Pre-comfort,
Comfort). For each status there will be a set of
values applied: main regulation setpoint, humidity
setpoint (if any humidity probe is present), CO2
CO2 [ppm]
75%%
PID signal
100%
%
MixChamber
VFD
100%
%
MAX

Содержание

Скачать