VTS Ventus VVS300 [6/47] Start up

VTS American VENTUS AVS 055 [6/47] Start up
uPC3 rel 1.8 11/2021
6
2. START UP
It is possible to load/update the application software of
the uPC3
controllers family with thw following methods:
Update via microUSB
Update from computer by using c.factory (via
USB or Ethernet connection)
Update with file transfer via FTP
Update with file transfer via microUSB
1- Connect to microUSB port
2- Open an My Computer USB Drive
3- Drag&drop the software update file from the
directory on the computer to the “UPGRADE” directory
on the uPC3 controller
4- Disconnect microUSB cable.
After disconnect cable autorun will start loading new
software.
5- Wait for the application to load and the VTS logo to
appear
6- After loading - Restart application press Alarm and
Enter go to Application and Restart application.
Update from computer using c.factory
On all uPC3 family controllers, the application program
can be loaded by using the c.factory software, with
direct connection to the controller via USB cable or
Ethernet network. To upload the application program,
proceed as follows:
Update via Ethernet connection:
Configure the computer and the uPC3 controller so
that they belong to the same LAN 1-Open c.factory
and select the application program fi le compiled
Inc.strategy tool (“.otr” fi le extension). The tool will list
the configurations defined in c.design. Select the
configuration to be loaded on the controller and click
“next”.
2- Select the files to be loaded on the controller and
“Ethernet connection” type. Select the MAC address
of the uPC3 controller being updated and click
“upload”.
3-At the end of the update procedure, the uPC3
controller restarts automatically with the new
application program (or new configuration)
Update via USB connection:
Connect the computer to the uPC3 controller via USB
cable using device USB port.