Installation & Maintenance : 6564868 08/2008
Installation Data
UNIT LIFTING
Employ lifting specialists
Local codes and regulations relating to the lifting of this type of equipment should
be observed
Use the appropriate spreader bars/lifting slings (provided by others) with the
holes/lugs provided
Attach individual lifting chains to each of the lifting eye bolts/lifting lugs provided;
each individual chain must be capable of lifting the whole unit
Do not use 1 chain between 2 lifting points to avoid load shift.
IMPORTANT
Only use lifting points provided.
Lifting hole/lug dimension: 40mm
Chains/slings MUST NOT interfere with the casing or fan assembly to avoid damage
Lift the unit slowly and evenly
IMPORTANT
If the unit is dropped, it should immediately be checked for damage and reported
to Airedale.
LIFTING DIMENSIONS
8 - 10 Fan
2300
A1
C
B
12 - 20 Fan
A1
C
B
C
A2
2300
A1 (Min) A2 (Min) B C
8 FAN mm 4000 N/A 520 3200
10 FAN mm 4000 N/A 846 3500
12 FAN mm 4000 5000 520 4000
14 FAN mm 5000 5000 520 4650
16 FAN mm 5000 5000 520 5000
18 FAN mm 6000 5000 520 5650
20 FAN mm 7000 5000 520 6650
IMPORTANT
For models with optional pumps fitted, a separate instruction will be provided.