OPTICHILL Chillers
Chillers
32
Installation & Maintenance : 6564868 08/2008
Installation Data
IMPORTANT
The following information is for general guidance; refer to the certified drawings
provided for installation.
ELECTRICAL DATA - HIGH EFFICIENCY
Standard Chiller - D
OPC500HED8 OPC525HED8 OPC550HED8 OPC600HED10 OPC650HED10
Unit Data
Nominal Run Amps (1) A 291 308 325 347 361
Maximum Start Amps (2) A 461 521 538 589 604
Rec Mains Fuse Size A 400 450 450 450 500
Mains Supply VAC 400 V 3 PH 50 Hz
Max Mains Incoming Cable Size mm² Direct to Bus Bar
Permanent Supply VAC 230 V 1 PH 50 Hz
Rec Permanent Fuse Size A 16 16 16 16 16
Max Permanent Incoming Cable Size mm² 4mm² Terminal
Control Circuit VAC 24V / 230VAC
Evaporator
Immersion Heater Rating W 100 100 100 100 100
External Trace Heating
Available (fitted by others) W 500 500 500 500 500
Condenser Fan - Per Fan
Quantity 8 8810 10
Standard AC Type
Full Load Amps A 3.8 3.8 3.8 3.8 3.8
Locked Rotor Amps A 11 11 11 11 11
Motor Size kW 1.8 1.8 1.8 1.8 1.8
Optional EC Type
Full Load Amps A 3.4 3.4 3.4 3.4 3.4
Motor Size kW 2.2 2.2 2.2 2.2 2.2
Compressor - Per Compressor
Quantity 1 + 1 1 + 1 1 + 1 1 + 1 1 + 1
Motor Size kW 74.5 / 74.5 83.4 / 74.5 83.4 / 83.4 91.8 / 83.4 91.8 / 91.8
Nominal Run Amps (1) A 130.4 / 130.4 147.3 / 130.4 147.3 / 147.3 161.5 / 147.3 161.5 / 161.5
Oil Heater Rating W 300 300 300 300 300
Start Amps (2) A 300 / 300 360 / 300 360 / 360 404 / 360 404 / 404
Type Of Start Star - Delta
OPTIONAL EXTRAS
Power Factor Correction
Nominal Run Amps (1) A 257 270 284 304 317
Maximum Start Amps (2) A 444 504 517 569 381
Recommended Mains Fuse A 400 450 450 450 500
Compressor Nom Run Amps - Per
Compressor
A 117 / 117 132 / 117 132 / 132 145 / 132 145 / 145
Closed Transition
Nominal Run Amps (1) A 291 308 325 347 361
Maximum Start Amps (2) A 461 521 538 589 604
Recommended Mains Fuse A 400 450 450 450 500
Compressor Nom Run Amps - Per
Compressor
A 130.4 / 130.4 147.3 / 130.4 147.3 / 147.3 161.5 / 147.3 161.5 / 161.5
Water Pump - ac Motor
Single Head or Run/Standby - Standard
Unit Nominal Run Amps (1) A 300 317 334 356 370
Recommended Mains Fuse A 400 450 450 450 500
Motor Size kW 4.0 4.0 4.0 4.0 4.0
Full Load Amps A 8.9 8.9 8.9 8.9 10.6
Single Head or Run/Standby - Larger
Unit Nominal Run Amps (1) A 306 322 339 361 382
Recommended Mains Fuse A 400 450 450 500 500
Motor Size kW 7.5 7.5 7.5 7.5 11.0
Full Load Amps A 14.4 14.4 14.4 14.4 21.0
Water Pump - Inverter Driven Motor
Single Head or Run/Standby - Standard
Unit Nominal Run Amps (1) A 302 319 336 358 372
Recommended Mains Fuse A 400 450 450 450 500
Motor Size kW 5.5 5.5 5.5 5.5 5.5
Full Load Amps A 11.0 11.0 11.0 11.3 11.3
Single Head or Run/Standby - Larger
Unit Nominal Run Amps (1) A 302 319 336 362 376
Recommended Mains Fuse A 400 450 450 450 500
Motor Size kW 5.5 5.5 5.5 7.5 7.5
Full Load Amps A 11.0 11.0 11.0 15.0 15.0
(1) Based at 12/7°C water and 35°C ambient with standard AC type fans.
(2) Starting amps refers to the Star connection only with standard AC type fans.