Electrical components Case
Drain pan
Evaporator
Air outlet frame
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The power cable and connecting cable are self-provided.
For series 122, 182, the power cable should be H05RN-F 3G 2.5mm
2
.
For series 242, the power cable should be H05RN-F 3G 4.0mm
2
.
For 122, 182(*EAA), the connecting cable should be H05RN-F 3G 2.0mm
2
+ 1x0.75mm
2
.
For the others the connecting cable should be H05RN-F 4G 0.75mm
2
.
All the cables shall have got the European authentication certificate. During installation, when the connecting cables break off,
it must be assured that the grouding wire is the last one to be broken off.
6. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no less than
3mm. Such means for disconnection must be incorporation in the fixed wiring.
7. The indoor unit installation height is at least 2.5m.
8. The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the diameter
of the wire should be enlarged according to the local wiring standard.
9. The waste battery shall be disposed properly.
1. Applicable ambient temperature range:
The machine is adaptive in following situation
6
Safety Precautions
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
ON-OFF Inverter
32/23 C
18/14 C
43/26 C
10/6 C
27 C
15 C
24/18 C
-7 C
32/23 C
18/14 C
43/26 C
-5 C
27 C
15 C
24/18 C
-10 C
Parts and Functions