Daikin EWYQ180DAYN [243/524] C1 temp readout

Daikin EWYQ230DAYN [243/524] C1 temp readout
ESIE06-05 The Digital Controller For Multiscroll Chillers
Part 2 – Functional Description 2–17
3
2
4
5
1
Screen 4
Screen 5
C1 TEMP.READOUT
SUCTION H11:007.4 °C
SUPERHEAT H11:007.3 °C
EEV PULS H11:0000PLS
Display Description
C1 TEMP. READOUT operational information EEV control of circuit 1
SUCTION C1 suction temp. in cooling mode of circuit 1
SUCTION H11 suction temp. in heating mode of compressor 1 of circuit 1
SUCTION H12 suction temp. in heating mode of compressor 2 of circuit 1
SUPERHEAT C1 actual superheat in cooling mode of circuit 1
SUPERHEAT H11 actual superheat in heating mode of coil 1 of circuit 1
SUPERHEAT H12 actual superheat in heating mode of coil 2 of circuit 1
EEV PULS C1 actual electronic expansion valve opening in cooling mode
EEV PULS H11 actual electronic expansion valve opening in heating mode of expan-
sion valve of coil 1
EEV PULS H12 actual electronic expansion valve opening in heating mode of expan-
sion valve of coil 2
C1 TEMP.READOUT
SUCTION H12:007.4 °C
SUPERHEAT H12:007.3 °C
EEV PULS H12:0000PLS