3.7 Fan Control
Purpose To regulate the high pressure.
There are two different methods used to control the HP.
Fan control based on ambient control: only at start-up, of each circuit, for the first 70 seconds
(default).
Fan control based on high pressure value, when fan ambient control is finished.
Schematic
overview
Fan control based
on Ambient
Temperature with
Standard Fans
Ambient based control for standard fans
During the first 70 seconds (default), after startup of a circuit, the fan control is based on the ambient
temperature. After this timer the fan control changes to high pressure control, based on high pressure
value.
Parameter 1 and 3 can be changed in the Service/Fan menu.
Fan control based
on high pressure
with standard fans
High pressure based control for standard fans.
After the first 70 seconds (default) fan control is based on high pressure value.
Start up unit
HP
Fan step in function
of HP value
< 7 °C
Amb.
Temp
7-17 °C > 17 °C
70 sec
No Yes
L
M
H
3 5°C
1 15°C
Low High
Ambient temp.
1 : Ambient setp A
3 : Ambient setp B
2 = 1 + 2°C
3 + 2°C
1 =
217°C
47°C