Part 2 – Functional Description 2–33
3
2
4
5
1
Floating Setpoint
CH. AI . SLOPE NTC
This screen allows modification of the floating setpoint, based on an additional NTC sensor, connected
to an analogue input.
Settings:
Remark: When mode “CH. AI SLOPE NTC” is selected, a changeable analogue input needs to be
programmed in the service/input output menu.
Floating Setpoint
CH. AI. SLOPE V-A
This screen allows modification of the floating setpoint based on an external voltage or current signal.
Settings:
Remark: When mode “CH. AI SLOPE V-A” is selected, a changeable analogue input needs to be
programmed in the service/input output menu.
MODE : Changeable analogue input slope NTC, floating setpoint based on
an additional NTC sensor
MAXPOS : Maximum value of positive floating setpoint correction
NEG : Maximum value of negative floating setpoint correction
RF : Reference value. At this ambient temperature there is no correction
of the setpoint.
SLOPE : This parameter is necessary to draw the angle of the curve.
_
MODE:CH.AI SLOPE NTC
MAXPOS:03.0 °C NEG:03.0 °C
RF:020.0 °C SLOPE:006.0 °C
FLOATING SETPOINT
MODE : Changeable analogue input slope V-A, floating setpoint based on
an external voltage or current signal
MAXPOS : Maximum value of positive floating setpoint correction
NEG : Maximum value of negative floating setpoint correction
RF : Reference value. At this percentage of the input signal there is no
correction of the setpoint.
SLOPE : This parameter is necessary to draw the angle of the curve.
_
MODE:CH.AI SLOPE V-A
MAXPOS:03.0 °C NEG:03.0 °C
RF:020.0 °C SLOPE:012.0 °C
FLOATING SETPOINT