The Digital Controller For Multiscroll Chillers ESIE06-05
2–88 Part 2 – Functional Description
3
1
2
4
5
2.15.8 DICN
DICN settings This screen allows modification of the DICN settings.
Settings:
Remark: NR OF SLAVES will only be visible when the unit is programmed as MASTER unit.
Slave addresses This screen allows modification of the slave addresses.
Settings:
MS OPTION : N: DICN is disabled
Y: DICN is enabled
UNIT : MASTER: unit is selected as master unit
SLAVE: unit is selected as slave unit
NR OF SLAVES : The number of slaves in the system has to be defined. (only
on the master unit)
_v
MS OPTION:N
DICN SETTING
UNIT:MASTER
NR OF SLAVES:1
Only on MASTER unit
ADD SL1 : Specify the D III address programmed in slave 1
ADD SL2 : Specify the D III address programmed in slave 2 (if present)
ADD SL3 : Specify the D III address programmed in slave 3 (if present)
Example: ADD SL1:1-01
_
ADD SL1:---
DICN SETTING