ESIE06-05 The Digital Controller For Multiscroll Chillers
Part 2 – Functional Description 2–31
3
2
4
5
1
2.8.4 Pump settings
Pump Control This screen allows modification of the pump control.
Settings:
Dual Pump This screen allows modification of the dual pump control.
Possible settings MODE:
PUMPLEADTIME : Time the water pump will operate before starting up the chiller
PUMPLAGTIME : Time the water pump will keep running after stopping the
chiller
DAILY ON : N: function disabled
: Y: activation of daily pump start
AT : Time of the daily ON function
PUMPCONTROL_v
PUMPLEADTIME
PUMPLAGTIME :060s
:020s
DAILY ON:N AT:00h00
AUTO ROTATION :
the sequence of the pump start is done based on the running hours
PUMP1 > PUMP2 : pump 1 will always start first
PUMP2 > PUMP1 : pump 2 will always start first
OFFSET ON RH : offset in running hours between pump1 and pump2 (only when auto-
rotation is selected)
DUAL PUMP_^
MODE:AUTO ROTATION
OFFSET ON RH :048h