Daikin EWYQ180DAYN [36/524] Electrical specifications ewyq080 260dayn

Daikin EWYQ230DAYN [36/524] Electrical specifications ewyq080 260dayn
General Outline ESIE06-05
1–24 Part 1 – System Outline
3
11
4
5
1.17 Electrical Specifications: EWYQ080-260DAYN
Electrical
specifications
The table below contains the electrical specifications.
EWYQ080
DAYN
EWYQ100D
AYN
EWYQ130DA
YN
EWYQ150DA
YN
EWYQ180D
AYN
EWYQ210D
AYN
EWYQ230DA
YN
EWYQ250D
AYN
Power supply Phase 3 3 3 3 3 3 3 3
Frequency Hz 50 50 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400 400 400
Voltage
Tole ra nc e
Minimum % -10%
Maximum % +10%
Unit Starting current A 201
(max.
240)
221 (max.
272)
161 (max.
269)
199 (max.
320)
221(max.
357)
221 (max.
368)
266 (max.
440)
266 (max.
468)
Nominal Running Current
Cooling
A 60 72 88 113 131 144 162 181
Maximum Running Cur-
rent
A 96 120 160 177 209 233 262 290
Recommended fuses according to
IEC standard 269-2
3x125gL 3x160gL 3x200gL 3x200gL 3x250gL 3x250gL 3x300gL 3x355gL
Fan Starting method Direct On-Line
Maximum Running Cur-
rent
A 1.5 1.5 1.4 2.1 2.1 2.1 1.6 1.6
Compressor Starting current A 195 215 158 195 195/215 215 215/260 260
Nominal Running Current
(RLA)
A 25/25 31/31 19/19 25/25 25/31 31/31 31/40 40/40
Maximum Running Cur-
rent
A 39 51 35 39 39/51 51 51/65 65
Starting method Direct On-Line
Control circuit Phase 1 1 1 1 1 1 1 1
Frequency Hz 50 50 50 50 50 50 50 50
Voltage V 230V
(supplied
by factory
installed
trans-
formers)
230V
(supplied
by factory
installed
transform-
ers)
230V (sup-
plied by fac-
tory
installed
transform-
ers)
230V (sup-
plied by fac-
tory installed
transform-
ers)
230V/24V
AC (sup-
plied by fac-
tory
installed
transform-
ers)
230V/24 V
AC (sup-
plied by
factory
installed
transform-
ers)
Crankcase heater
(E1/2HC)
W 2x75 2x75 4x65 4x75 4x75 4x75 4x75 4x75

Содержание

Скачать