ESIE06-05 Functional Control for a Standalone Unit
Part 2 – Functional Description 2–147
3
2
4
5
1
Practical example:
DICN Thermostat
function in heating
The illustration below shows the thermostat inlet control in heating mode for a DICN network.
= Setpoint
Condition Result
If evaporator inlet temperature (Master)
--> active inlet setpoint +A
Loadup request A1 Loadup is executed and loadup timer is
put on maximum.
If evaporator inlet temperature (Master)
--> active inlet setpoint + A +B +C
Loadup request A2 Loadup nr1 is executed and loadup
timer is put on maximum.
Loadup nr2 is executed and loadup
timer - 15 sec.
If evaporator inlet temperature (Master)
--> active inlet setpoint + A + 2x(B+C)
Loadup request A3 Loadup nr1 is executed and
loadup&loaddown timer is put on maxi-
mum.
Loadup nr2 is executed at loadup timer
- 15 sec
Loadup nr3 is executed at loadup timer
- 30 sec