Daikin EWYQ180DAYN [441/524] Overview of most common problems

Daikin EWYQ230DAYN [441/524] Overview of most common problems
ESIE06-05 Procedure for Software Upload
Part 3 – Troubleshooting 3–41
33
4
5
1
4.5 Overview of most common problems
PCASO flash
Symptom Possible cause
1. Not possible to start upload
No connection to Main PCB nr 1
Main PCB nr 1 has no power
Wrong adapter cable is used. (“R” label)
2. Upload stops after certain %
Serial connection has been cut
3.
ex. Debugmonitor is also running => close program
Visa software is running (can be checked status bar next to time )=>
close program
4. After upload never display on remocon or
continuously “STARTUP BUSY”
Remocon has been uploaded with wrong mot file.
Remocon Main and Sub have same address (ex. Main & Main or Sub &
Sub)
5. Not possible to select the different software
files from different directories
The different software files should be put in one directory.