Daikin EWYQ180DAYN [491/524] External static unit pressure ewaq130 210 dayn p b

Daikin EWYQ230DAYN [491/524] External static unit pressure ewaq130 210 dayn p b
ESIE06-05 Pre-Test Run Checks
Part 4 – Commissioning and Test Run 4–31
3
4
5
1
1.17 External Static Unit Pressure: EWAQ130-210 DAYN (P-B)
External Static
Pressure
The illustration below shows the water pressure drop through evaporator for EWAQ130-210 DAYN
(P-B).
Symbols The table below describes the symbols.
Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also
minimum and maximum allowed water flowrange. See "Technical Specifications:
EWAQ080-260DAYN" on page 1–5.
0
50
100
150
200
250
300
ExternalStaticPressureUnit[kPa]
150 250 350 450 550 650 750 850
WaterFlow[l/min]
3
4
1
2
Symbol Description
(1) EWAQ130 DAYN*+0PSP
(2) EWAQ150 DAYN*+0PSP
(3) EWAQ180 DAYN*+0PSP
(4) EWAQ210 DAYN*+0PSP

Содержание