Daikin EWYQ180DAYN [435/524] Software upload procedure pcasoflash

Daikin EWYQ180DAYN [435/524] Software upload procedure pcasoflash
ESIE06-05 Procedure for Software Upload
Part 3 – Troubleshooting 3–35
33
4
5
1
4.3 Software upload procedure: PCASOflash
Introduction The upload of the parameters can be executed on Main PCB nr 1 only.
The upload of the Software and parameters
can be executed on Main PCB nr 1 only. After this the
software is distributed by the Main PCB nr 1 towards the Main PCB nr 2, the extension PCB and
towards the Main and sub remocon.
(If PCASOflash is not installed yet: refer to chapter “install software PCASOflash”)
PCASOflash:
manual upload
Remark: all lgc and lng and par files should be put in 1 directory!
Action Result
Connect wires:
Communication: X49A ÙRS-232C
Cable incl drive assy+ adapter cable with
label “R”
Power: X1A Ù 230V
Remark: PCB should be continuously
powered.
Result:
HAP is blinking
Remark: In case HAP is continuously On, then the
wrong adapter cable is used.
2. Start PCASOflash.exe Result: PCASO flash main window
By default: “Upload software sheet” is selected
X49A Serial communication
X1A power (230V)
HAP