3.18.3 Anti-freeze function by refrigerant gas temperature
Function only in
cooling
Activation :
If refrigerant gas temperature is < REFR TEMP SET continuously for 10 seconds.
Action:
Switch off/on the unit (first time in 30 min --> no alarm).
If above condition is satisfied twice in 30 minutes --> switch off unit on alarm.
Reset:
Reset possible if refrigerant temperature rises above -2.5 °C.
This control will be masked during below operation status.