Functional Control for a Standalone Unit ESIE06-05
2–142 Part 2 – Functional Description
3
1
2
4
5
3.14 Changeable analogue inputs
Introduction Four changeable analogue inputs are available and can be assigned to four different functions in the
service menu.
Function overview Possible settings for changeable analogue inputs.
None
-No status function is allocated to this analogue input.
Status
-Displays the analogue input value in the I/O menu.
Floating Setpoints
-Select the signal type used for the floating setpoint function.
Temperature
- An additional temperature sensor can be connected to the controller and will be displayed in the
I/O menu (only NTC type can be selected).
Possible analogue input types:
0-20 mA
4-20 mA
0-1V
0-5V
0-10V
NTC Type1
NTC Type2
NTC Type3
NTC Type4
The analogue input can also be programmed as a digital input.
Possible settings analogue inputs:
Digital inputs
- DI STATUS
- DI REM COOL/HEAT
- DI CAP.LIM 25%/50%/75%
- DI CAP LIM SET
- DI FREE COOLING
When a DI signal is selected the AI type will automatically go to DIGITAL INP. Type.
Remark : The digital input will close when an 5Vdc signal is given to the controller.