The Digital Controller For Multiscroll Chillers ESIE06-05
2–70 Part 2 – Functional Description
3
1
2
4
5
EEV Control Adjust
Cool / Heat
This screen allows modification of the adjust cool/heat pulses.
Settings:
Low Ambient EEV
Control
This screen allows modification of the Low Ambient function.
Settings:
ADJUST COOL : After the initializing process, if the compressor starts up in cooling mode,
it goes to the specified output for the electronic expansion valve. After
reaching above ADJUST COOL EV opening, it will go to normal
superheat control.
ADJUST HEAT : After the initializing process, if the compressor starts up in heating mode,
it goes to the specified output for the electronic expansion valve. After
reaching above ADJUST HEAT EV opening, it will go to normal
superheat control.
SAMPLING TIME : Sampling time for the expansion valve control.
_
ADJUST COOL:0800pls
ADJUST HEAT:0300pls
SAMPLING TIME:003s
EEV CONTROL
ADJUST HEAT : After initializing process, if the compressor starts up in heating
mode and the ambient temperature is below the HEAT AMB.
CONST setpoint, it goes to the specified output for the electronic
expansion value. After reaching above ADJUST HEAT EV
opening, it will go to normal superheat control.
HEAT AMB. CONST : Ambient setpoint for the low ambient condition function.
_
LOW AMB.CONDITION
ADJUST HEAT:150pls
HEAT AMB.CONST:005.0 °C
EEV CONTROL