ESIE06-05 The Digital Controller For Multiscroll Chillers
Part 2 – Functional Description 2–73
3
2
4
5
1
EEV Feed Forward
Control
This screen allows modification of the EEV FF control in Heating mode.
Settings:
EEV Feed Forward
Low Ambient
Control
This screen allows modification of the EEV FF control in cooling heating with low ambient
temperatures.
Settings:
FF CONTROL UP : If the compressor load goes up, the controller will change the EEV
opening.
Output pulses= Current pulses x “FF CONTROL UP”
FF CONTROL DOWN : If the compressor load goes down, the controller will change the
EEV opening.
Output pulses= Current pulses / “FF CONTROL DOWN”
_
FF NORMAL UP :1.5
FF NORMAL DOWN:1.7
HEAT EEV CONTROL
FF LOW AMB. UP : If the compressor load goes up AND the ambient temperature is
below the HEAT AMB. CONST setpoint, the controller will change
the EEV opening.
Output pulses= Current pulses x “FF LOW AMB. UP”
FF LOW AMB. DOWN : If the compressor load goes down AND the ambient temperature
is below the HEAT AMB. CONST setpoint, the controller will
change the EEV opening.
Output pulses= Current pulses / “FF LOW AMB. DOWN”
_
FF LOW AMB.UP :2.2
FF LOW AMB.DOWN:2.2
HEAT EEV CONTROL