Troubleshooting by Indication on the Remote Controller Si39-501
218 Troubleshooting
3.41
U2
Outdoor Unit: Power Supply Insufficient or
Instantaneous Failure
Remote
Controller
Display
U2
Applicable
Models
RXQ5MA~48MA
Method of
Malfunction
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Decision
Conditions
When the capacitor above only has a voltage of 380 V or less.
Supposed
Causes
Power supply insufficient
Instantaneous failure
Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Main circuit wiring defect