Daikin RXQ26MAY1 [98/344] Special control

Daikin RXQ46MAY1 [98/344] Special control
Si39-501 Special Control
Function 87
3. Special Control
3.1 Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made.
3.1.1 Startup Control in Cooling Operation
Thermostat ON
Pressure equalization
control prior to startup
Startup control
STEP1 STEP2
Compressor OFF
52Hz
+OFF +OFF
+2 steps/20 sec.
(until Pc - Pe>0.39MPa is achieved)
Outdoor unit fan OFF OFF
+1 step/15 sec. (when Pc>2.16MPa)
-1 step/15 sec. (when Pc<1.77MPa)
Main motorized valve (EV1) 0 pls 2000 pls 2000 pls
Subcooling motorized valve
(EV2)
0 pls 0 pls 0 pls
Hot gas bypass valve
(SVP)
ON (RXQ5MA models)
OFF (RXQ8~16MA models)
ON ON
Receiver gas discharging
valve (SVG)
OFF OFF OFF
Non-operating unit liquid
pipe stop valve (SVL)
ON ON ON
Ending conditions
RXQ5MA models
Pc - Pe<0.20MPa
A lapse of three
minutes
RXQ8~16MA models
A lapse of 15 sec.
A lapse of 5 sec.
A lapse of 320 sec.
Pc - Pe>0.39MPa
OR
OR