Daikin RXQ26MAY1 Сервис мануал онлайн [304/344] 545648

Daikin RXQ40MAY1 Сервис мануал онлайн [304/344] 545799
Si39-501 List of Electrical and Functional Parts
Appendix 293
Item Name Symbol
Model
RXQ12MAY1 RXQ14MAY1 RXQ16MAY1
Compressor
Inverter
Type
M1C
JT1G-VDKYR@T
OC protection
device
13.5A
STD 1
Type
M2C
JT170G-KYE@T
OC protection
device
15.0A
STD 2
Type
M3C
JT170G-KYE@T
OC protection
device
15.0A
Fan motor
OC protection
device
M1F 1.8A
Electronic expansion valve (Main) Y1E Fully closed: 0pls Fully open: 2000pls
Electronic expansion valve (Subcool) Y2E Fully closed: 0pls Fully open: 2000pls
Pressure
protection
High pressure
switch
For M1C S1PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M2C S2PH OFF: 4.0 MPa ON: 3.0±0.15MPa
For M3C S3PH
OFF: 4.0 MPa
ON: 3.0±0.15MPa
Low pressure sensor SLNPL OFF: 0.07MPa
Fusible plug open: 70~75°C
Temperature
protection
Discharge gas temperature
protection
(Discharge pipe thermistor)
R3T OFF: 135°C
Inverter fin temperature
protection
(Radiator fin thermistor)
R1T OFF: 98°C
Others Fuse
For main PC
board
F1U 250V AC 10A Class B
F2U 250V AC 10A Class B
For Noise filter
PC board
F1U 250V AC 5A Class B
+
0
0.12
+
0
0.12
+
0
0.12

Содержание

Скачать