Special Control Si39-501
90 Function
3.4 Standby
3.4.1 Restart Standby
Used to forcedly stop the compressor for a period of five minutes, in order to prevent the frequent ON/OFF of the
compressor and equalize the pressure within the refrigerant system.
* Actuators are based on RXQ16MA.
3.4.2 Crankcase Heater Control
In order to prevent the refrigerant from melting in the compressor oil in the stopped mode, this mode is used to control
the crankcase heater.
Actuator Operation Remarks
Compressor OFF
Outdoor unit fan
Ta>30°C: STEP4
Ta30°C: OFF
Main motorized valve (EV1) 0 pls
Subcooling motorized valve (EV2) 0 pls
Hot gas bypass valve (SVP) OFF
In the case of RXYQ5MA, this valve
turns ON.
Receiver gas discharging valve (SVG) OFF
Non-operating unit liquid pipe stop
valve (SVSL)
ON
Ending conditions 5 min.