5.3 Example of Connection
Example of connection
(Connection of 8 indoor units Heat pump system)
One outdoor
unit installed
(RXQ5~16)
Branch with refnet joint
Branch with refnet joint and refnet header
Branch with refnet header
a
ABCDEFG
ABC
D
EFG
bcdef
g
hi j kl mn
1234567
8
H2
H1
P
Outdoor unit
REFNET joint (A-G)
Indoor units (1-8)
H1
H1
H2
H2
a a
i
b
a
i
b
cde f
g
h
123456
Outdoor unit
Outdoor unit
REFNET joint (A • B)
Indoor units (1-8)
cde f
g
h
123456
Indoor units (1-8)
Refnet header
Refnet header
k
j
78
k
j
78
H1
H2
H2
Outdoor unit
Refnet header
Indoor units (1-8)
cde
f
g
h
b
1234567
8
8
abcdef
g
8
H2
H1
H3 H3
P
Indoor units (1-8)
Outdoor unit
REFNET joint (A-G)
REFNET joint (A • B)
hi j kl mn
1234567
First outdoor
branch
H1
H3
a
Outdoor unit
Refnet header
Indoor units (1-8)
cde
f
g
h
b
1234567
When multiple
outdoor units
installed
(RXQ18~)
(
2)
If the system capacity is RXQ18 or more,
re-read to the first outdoor branch as seen from
the indoor unit.
Maximum
allowable
length
Between outdoor
(
2)
and indoor units
Between outdoor branch and outdoor unit
(Only for RXQ18 or more)
Between outdoor and indoor units
Between indoor and indoor units
Between outdoor and outdoor units
Actual pipe length
Actual pipe length
Difference in height
Difference in height
Difference in height
Equivalent length
Total extension length
Pipe length between outdoor (2) and indoor units 150m
Example unit 8: a + b + c + d + e + f + g + p 150m
Example unit 8: b + c + d + e + f + g + p 40m (See Note 2 - Next page)
Equivalent pipe length between outdoor (2) and indoor units 175m Note 1 (assume equivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, calculation purposes)
Difference in height between outdoor and indoor units (H1) 50m (Max 40m if the outdoor unit is below)
Difference in height between indoor units (H2) 15m
Difference in height between outdoor unit (main) and outdoor unit (sub) (H3) 5m
Pipe length from first refrigerant branch kit (either REFNET joint or REFNET header ) to indoor unit 40m (See Note 2 - Next page)
Total piping length from outdoor unit (2) to all indoor units 510m
Allowable
height
length
Allowable length after the branch
Refrigerant branch kit selection
Pipe size selection
Example unit 8: a + i 150m
Example unit 6: a + b + h 150m, unit 8: a + i + k 150m
Example unit 8: i 40mExample unit 6 : b + h 40m, unit 8 : i + k 40m
r 10m (Approximately length: max 13m)
s 10m (Approximately length: max 13m)
t 10m (Approximately length: max 13m)
Refrigerant branch kits can only be
used with R-410A.
How to select the REFNET joint
When using REFNET joints at the first branch counted from the outdoor unit side.
Choose from the following table in accordance with the capacity of the outdoor unit.
Piping between outdoor unit and refrigerant branch kit (part A)
Match to the size of the connection piping on the outdoor unit.
Outdoor unit connection piping size
How to calculate the additional refrigerant
to be charged
If a negative result is gotten for R from the formula at right, no refrigerant
needs to be added.
Additional referigerant to be charged R (Kg)
(R should be rounded off in units of 0.1Kg.)
Piping between outdoor branch
and outdoor unit (part C)
Piping between outdoor branches (part B)
Piping between outdoor unit and refrigerant branch kit (part A)
RXQ5 type
RXQ8, 10, 12 type
RXQ14~24 type
RXQ26 type~
KHRP26M22T
KHRP26M33T
KHRP26M72T
KHRP26M73T + KHRP26M73TP
For REFNET joints other than the first branch, select the proper branch kit model based on the total capacity index.
< 200
200 x< 290
290 x< 640
640
KHRP26M22T
KHRP26M33T
KHRP26M72T
KHRP26M73T + KHRP26M73TP
How to select the REFNET header
Choose from the following table in accordance with the total capacity of all the indoor units connected below the REFNET header.
Note: 250 type cannot be connected below the REFNET header.
< 200
< 290
290 x< 640
640
KHRP26M22H (Max. 4 branch)
KHRP26M33H (Max. 8 branch)
KHRP26M72H (Max. 8 branch)
KHRP26M73H (Max. 8 branch) + KHRP26M73HP
How to select an outdoor branch kit (needed if the outdoor unit capacity type is RXQ18 or more.)
Choose from the following table in accordance with the number of outdoor units.
2 unit
3 unit
BHFP22MA90
BHFP22MA135
example in case of REFNET joint C; indoor units 3 + 4 + 5 + 6 + 7 + 8
example in case of REFNET joint B; indoor units 7 + 8,
example in case of REFNET header; indoor units 1 + 2 + 3 + 4 + 5 + 6
example in the case of REFNET header ; indoor units 1 + 2 + 3 + 4 + 5 + 6 + 7 + 8
Example of downstream indoor units
φ9.5 × 0.80
φ12.7 × 0.80
φ15.9 × 0.99
φ19.1 × 0.80
RXQ5 type
RXQ8 type
RXQ10, 12 type
RXQ14, 16, 18 type
RXQ20~24 type
RXQ26~36 type
RXQ38~48 type
φ15.9 × 0.99
φ19.1 × 0.80
φ22.2 × 0.80
φ28.6 × 0.99
φ34.9 × 1.21
φ41.3 × 1.43
Gas pipe
indoor capacity index
Piping size (outer diameter x minimum thickness)
Liquid pipe
φ12.7 × 0.80
φ15.9 × 0.99
φ19.1 × 0.80
Piping between refrigerant branch kit and indoor unit
Match to the size of the connection piping on the indoor unit.
Indoor unit connection piping size
φ6.4 × 0.80
φ9.5 × 0.80
20, 25, 32, 40, 50 type
63, 80, 100, 125 type
200 type
250 type
φ12.7 × 0.80
φ15.9 × 0.99
φ19.1 × 0.80
φ22.2 × 0.80
Piping between outdoor branch and outdoor unit (part C)
Gas pipe
outdoor capacity type
Piping size (outer diameter x minimum thickness)
Liquid pipe
φ12.7 × 0.80
φ9.5 × 0.80
RXQ8 type
RXQ10, 12 type
RXQ14, 16 type
φ19.1 × 0.80
φ22.2 × 0.80
φ28.6 × 0.99
a: φ19.1 × 30m
b: φ15.9 × 10m
c: φ09.5 × 10m
d: φ9.5 × 10m
e: φ9.5 × 10m
f : φ9.5 × 10m
g: φ16.4 × 10m
h: φ16.4 × 20m
i : φ12.7 × 10m
j : φ16.4 × 10m
k: φ16.4 × 19m
φ15.9 × 0.99
φ19.1 × 0.80
24HP
26HP
φ28.6 × 0.99
φ34.9 × 1.21
(Unit : mm)
(Unit : mm)
(Unit : mm)
R=
+
indoor capacity index
Refrigerant branch kit name
Number of outdoor units
Branch kit name
Outdoor unit capacity type Refrigerant branch kit name
indoor capacity index
Refrigerant branch kit name
Gas pipe
Outdoor unit capacity type
Piping size (outer diameter x minimum thickness)
Liquid pipe
Gas pipe
outdoor capacity index
Piping size (outer diameter x minimum thickness)
Liquid pipe
Gas pipe
indoor capacity type
Piping size (outer diameter x minimum thickness)
Liquid pipe
+
++
+
+
If the outdoor unit is
RXQ34 type and the
piping lengths are as at
right
R= 30 0.25 + 10 0.17 + 10 0.11 + 40 0.054 + 49 0.022 + 0 =13.538
ba c+d+e+f g+h+j+ki
13.5
NOTE :
Total length (m)
of liquid piping
size at φ22.2
×0.35
Total length (m)
of liquid piping
size at φ19.1
×0.25
Total length (m)
of liquid piping
size at φ15.9
×0.17
Total length (m)
of liquid piping
size at φ12.7
×0.11
Total length (m)
of liquid piping
size at φ9.5
×
0.054
Total length (m)
of liquid piping
size at φ6.4
×
0.022
Model name
RXQ8~32 type
RXQ5, 34~48 type
1 kg
0 kg
Amount of refrigerant
Example for refrigerant branch using REFNET joint and REFNET header for RXQ34 type
A
B
AB
Caution
The thickness of the pipes in the table shows the requirements of Japanese High
Pressure Gas Control low. (As of Jan. 2003)
The thickness and material shall be selected in accordance with local code.
For an outdoor unit multi installation (RXQ18~48 type), make the
settings in accordance with the following figure.
Use the outdoor unit multi connection piping kit that
is sold separately as an option (BHFP22MA90·135)
for the multi installation of outdoor units.Selection
method is as shown in the right table.
Never use the outdoor unit multi connection piping
kit (BHFP22M90·135) that are sold separately as
an option of M-type or T-joint.
(
1) ” indicates the outdoor unit multi connection
piping kit.
Install the joint part ( part in the figure) of the outdoor
unit multi connection piping kit horizontally with attention
to the installation restrictions described in “connection
the refrigerant piping”.
r
t
s
Outdoor unit
Temper grade
O Type 1/2 H Type
Copper tube O.D
φ6.4 φ9.5
0.80 0.80 0.80 0.99 0.80 0.80 0.88 0.99 1.10 1.21 1.32 1.43
φ12.7 φ15.9 φ19.1 φ22..2 φ25.4 φ28.6 φ31.8 φ34.9 φ38.1 φ41.3
Copper tube W.T
(Minimum
requirement)
(Unit : mm)
Actual pipe length
Equivalent length
Piping length from outdoor branch to outdoor unit 10m
Piping length from outdoor branch to outdoor unit 13m
Piping between refrigerant branch kits
Select from the following table in accordance with the total capacity of all the
indoor units connected below this.
Do not let the connection piping exceed the refrigerant piping size chosen by
general system model name.
φ9.5 × 0.80
x< 150
150 x< 200
200 x< 290
290 x< 420
420 x< 640
640 x< 920
920
φ15.9 × 0.99
φ19.1 × 0.80
φ22.2 × 0.80
φ28.6 × 0.99
φ34.9 × 1.21
φ41.3 × 1.43
Piping between outdoor branches (part B)
Select from the following table in accordance with the total capacity of all the
outdoor units connected above this.
(Unit:mm)
(Unit:mm)