Daikin REYQ48MY1B [139/312] Multi outdoor units connection

Daikin FXNQ25MVE [139/312] Multi outdoor units connection
Field Setting Si39-302
128 Test Operation
& Set Cool / Heat for More Than One Outdoor Unit System Simultaneously in Accordance with Unified
Master Outdoor Unit by Indoor Unit Remote Controller
#
Install the outdoor unit external control adapter on either the outdoor-outdoor, indoor-
outdoor, or transmission line.
#
Set outdoor unit PC board DS1-1 to “Indoor” (factory set).
#
In setting mode 1, set the outdoor unit you want to give cool/heat selection permission to as
the group master, and set the other outdoor units as group slave units.
#
Set the outdoor unit external control adapter SS1 to Unified (factory set) or Cool, and SS2 to
No (factory set).
Multi outdoor units connection