Daikin REYQ48MY1B [215/312] Malfunction of transmission between indoor units

Daikin FXLQ25MVE [215/312] Malfunction of transmission between indoor units
Troubleshooting by Indication on the Remote Controller Si39-302
204 Troubleshooting
2.42
U4
Malfunction of Transmission Between Indoor Units
Remote
Controller
Display
U4
Applicable
Models
All model of indoor unit
RXYQ5~48M
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor and outdoor units is normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
!
Indoor to outdoor,outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
or wrong wiring
!
Outdoor unit power supply is OFF
!
System address doesn’t match
!
Defect of indoor unit PC board
!
Defect of outdoor unit PC board