Daikin REYQ48MY1B [169/312] Indoor unit malfunction of drain level control system 33h

Daikin REYQ28MY1B [169/312] Indoor unit malfunction of drain level control system 33h
Troubleshooting by Indication on the Remote Controller Si39-302
158 Troubleshooting
2.3
A3
Indoor Unit: Malfunction of Drain Level Control
System (33H)
Remote
Controller
Display
A3
Applicable
Models
FXCQ, FXFQ, FXSQ, FXAQ, FXKQ, FXHQ (Option) , FXMQ (Option)
Method of
Malfunction
Detection
By float switch OFF detection
Malfunction
Decision
Conditions
When rise of water level is not a condition and the float switch goes OFF.
Supposed
Causes
!
220~240V power supply is not provided
!
Defect of float switch or short circuit connector
!
Defect of drain pump
!
Drain clogging, upward slope, etc.
!
Defect of indoor unit PC board
!