8 | Electrical installation
Installer reference guide
105
ERLA03DAV3 + EHFH03S18DJ3V
Daikin Altherma 3 R F
4P596806-1A – 2020.05
1245
S6S
S7S
S8S
S9S
3
A
B
A
B
A8P
X801M
a
1 2 3 4 5
a Installation of EKRP1AHTA is required.
4 Fix the cable with cable ties to the cable tie mountings.
8.3.11 To connect the safety thermostat (normally closed contact)
Wires: 2×0.75mm²
Maximum length: 50m
Safety thermostat contact: 16VDC detection (voltage supplied by PCB).
The voltage-free contact shall ensure the minimum applicable load of
15VDC, 10mA.
[A.2.1.6]=3 (Forced off contact = Thermostat)
1 Open the following (see "6.2.4To open the indoor unit"[454]):
1 Top panel
1
2
3
2 Upper front panel
3 Upper switch box cover
2 Open the service cover. See "6.2.2To open the outdoor unit"[453].
3 Connect the safety thermostat (normally closed) cable to the appropriate
terminals as shown in the illustration below.