Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Field settings table
Installer setting at variance with
default value
A.6.1 [3-00] R/W 0: No
1: Yes
└─ Pwr consumpt. Control
A.6.3.1 [4-08] R/W
0: No limitation
1: Continuous
2: Di
g
ital in
p
uts
A.6.3.2 [4-09] R/W
0: Current
1: Powe
r
A.6.3.3 [5-05] R/W 0~50 A, step: 1 A
50
A
A.6.3.4 [5-09] R/W 0~20 kW, step: 0,5 kW
20 kW
└─ Averaging time
A.6.4 [1-0A] R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─ Ext amb. sensor offset
A.6.5 [2-0B] R/W -5~5°C, step: 0,5°C
0°C
└─ Emergency
A.6.C R/W
0: Manual
1: Automatic
└─ Disable protective Function
A.6.D Disable protections R/W
0: No
1: Yes
└─ Overview settings
A.8 [0-00] R/W [9-05]~min(45,[9-06])°C, step: 1°C
35°C
A.8 [0-01] R/W [9-05]~[9-06]°C, step: 1°C
50°C
A.8 [0-02] R/W 10~25°C, step: 1°C
15°C
A.8 [0-03] R/W -40~5°C, step: 1°C
-10°C
A.8 [0-04] R/W [9-07]~[9-08]°C, step: 1°C
8°C
A.8 [0-05] R/W [9-07]~[9-08]°C, step: 1°C
12°C
A.8 [0-06] R/W 25~43°C, step: 1°C
35°C
A.8 [0-07] R/W 10~25°C, step: 1°C
20°C
A.8 [0-0B] R/W 35~[6-0E]°C, step: 1°C
55°C
A.8 [0-0C] R/W 45~[6-0E]°C, step: 1°C
60°C
A.8 [0-0D] R/W 10~25°C, step: 1°C
15°C
A.8 [0-0E] R/W -40~5°C, step: 1°C
-10°C
A.8 [1-00] R/W -40~5°C, step: 1°C
-10°C
A.8 [1-01] R/W 10~25°C, step: 1°C
15°C
A.8 [1-02] R/W
[9-01]~[9-00], step: 1°C
35°C
A.8 [1-03] R/W [9-01]~min(45, [9-00])°C , step: 1°C
25°C
A.8 [1-04] R/W 0: Disabled
1: Enabled
A.8 [1-05] R/W 0: Disabled
1: Enabled
A.8 [1-06] R/W 10~25°C, step: 1°C
20°C
A.8 [1-07] R/W
25~43°C, step: 1°C
35°C
A.8 [1-08] R/W [9-03]~[9-02]°C, step: 1°C
22°C
A.8 [1-09] R/W [9-03]~[9-02]°C, step: 1°C
18°C
A.8 [1-0A] R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
A.8 [1-0B] R/W 3~66°C, step: 1°C
5°C
A.8 [1-0C] R/W 3~10°C, step: 1°C
5°C
A.8 [1-0D] R/W 3~10°C, step: 1°C
5°C
A.8 [1-0E] R/W 3~10°C, step: 1°C
5°C
A.8 [2-00] R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunda
y
A.8 [2-01] R/W 0: No
1: Yes
A.8 [2-02] R/W 0~23 hour, step: 1 hour
1
A.8 [2-03] R/W
60°C
A.8 [2-04] R/W 40~60 min, step: 5 min
40 min
A.8 [2-05] R/W 4~16°C, step: 1°C
12°C
kW value
Mode
Amp. value
What is the disinfection target temperature?
How long must the tank temperature be maintained?
Room antifrost temperature
What is the desired delta T in heating for the additional zone?
What is the desired delta T in cooling for the main zone?
What is the desired delta T in cooling for the additional zone?
When should the disinfection function be executed?
Should the disinfection function be executed?
When should the disinfection function start?
Low ambient temp. for LWT main zone cooling WD curve.
High ambient temp. for LWT main zone cooling WD curve.
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
What is the averaging time for the outdoor temp?
What is target delta T in heating?
Low ambient temp. for LWT main zone heating WD curve.
High ambient temp. for LWT main zone heating WD curve.
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
Weather dependent cooling of the main leaving water temperature zone.
Weather dependent cooling of the additional leaving water temperature zone
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
High ambient temp. for DHW WD curve.
Low ambient temp. for DHW WD curve.
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Type
4P596814-1 - 2019.10
(*1) EHFH03S18DJ3V + EKHVCONV3_
(*2) EHFH03S18DJ3V