6.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
c
c
d
b
a
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
It is recommended to provide at least 150 mm of free space below the unit
(300mm for heavy snowfall areas). Additionally, make sure the unit is positioned at
least 100mm above the maximum expected level of snow. If necessary, construct
a pedestal. See "6.3Mounting the outdoor unit"[457] for more details.
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.
By default, the outdoor unit heat pump can operate until –7°C. Depending on the
installation area, this can be lowered to –15°C by modifying the BUH only
ambient temp. ([8-0E]) field setting. This setting can also be changed via the
menu structure. See the installation manual of the indoor unit for how to change
the setting.
Additionally, in areas with ambient temperatures between –7°C and –15°C, and
depending on the altitude of the unit, the installation of a bottom plate heater
(EKBPHT03D) may be required to guarantee outdoor unit operation.
500
1000
1500
2000
-10 -5
-7
0
A (m)
T (C°)
2500
-15
e
d
c
a
b
A Altitude
T Temperature
a No special installation requirements
b Below 1000m, no bottom plate heater is installed. Set [8-0E]=–15°C.
c Unit between 1000m and 1500m altitude — Bottom plate heater required. Set [8-0E]=–15°C.
d Unit between 1500m and 2000m altitude — Bottom plate heater required and set [8-0E]=–15°C. If the
unit is within 3km of any lakes or rivers, [8-0E]=–7°C.
e Outdoor unit operation not possible below –7°C (backup heater operation only). [8-0E]=–7°C.