Sagi KUBA (внутренний агрегат) Инструкция по эксплуатации онлайн [28/116] 273193

Sagi KUJAA (внутренний агрегат) Инструкция по эксплуатации онлайн [28/116] 273188
12
Use the up and down keys to display the function [Loc].
Press the key on/sby/enter to confirm your selection and activate/de-activate the function.
Press the keys simultaneously for over 5 seconds to unlock the keyboard.
You can leave the programming phase by waiting for 30 seconds without operating on the card, or pressing for 5 seconds.
In both cases, there you will hear 3 consecutive, short beeps and the display will temporarily show [ESC].
PROBE READING MANUAL PRINTING: together with TSP printing terminal
Hold the key menu pressed for over 3 seconds to gain access to the quick-access function.
The display shows the first smart function option.
It blinks at high frequency.
Use the up and down keys to display the function [Prt].
Press the key on/sby/enter to confirm your selection and activate the function.
You can leave the programming phase by waiting for 30 seconds without operating on the card, or pressing for 5 seconds.
In both cases, there you will hear 3 consecutive, short beeps and the display will temporarily show [ESC].
PARAMETER CONFIGUTATION
Hold the key menu pressed for over 3 seconds to gain access to the quick-access function.
The display shows the first smart function option.
It blinks at high frequency.
Use the up and down keys to display the function [Par].
Press the on/sby/enter key to enter the parameter configuration mode.
Enter the password to gain access.
The display shows the password setting mode [00]
Use the up and down keys to select the password “65
Press the on/sby/enter key to confirm your selection.
If the password is correct, the display shows the first parameter in the configuration list.
Use the up and down keys to scroll the controller parameters
Press the on/sby/enter key to confirm your selection.
Use the keys up and down to select the new value