Sagi KUBA (внутренний агрегат) [31/116] Alarms

Sagi KIAA (внутренний агрегат) [31/116] Alarms
15
DEFAULT PARAMETER RECOVERY
Information accessible to qualified staff only
On starting the appliance, a “LAMPTEST” phase will start.
If you press the on/sby/enter key 3 times consecutively during this phase, all default parameters
will be reset.
The display shows [rLd] indicating the reset of the values pre-set by the manufacturer.
ATTENTION: the default values in memory refer to the configurations (TN, BT, PV) exclusively.
ALARMS
APPLIANCE WITH BROKEN PROBES
Room probe error
If the room probe is broken or the relevant connection interrupted, the display shows the label [E0].
The appliance keeps operating in storing according to the values given to parameters C5 and C6.
The inner fan keeps operating according to the value given to F7.
The defrost control is automatically inhibited and the card self-calibration process de-activated.
Evaporator fan error
If the evaporator probe is broken or the relevant connection interrupted, the display shows the label [E1].
Defrost starts after a period of time set through “d0” starting from the last defrost cycle.
The inner fan operates according to the value given to parameter F3
The defrost control is automatically inhibited and the card self-calibration process de-activated.
HIGH TEMPERATURE ALARM
If the room temperature exceeds the setpoint, the label [AH] and the temperature reached
alternate on the display. The buzzer sounds.
Press up to display the duration of the event causing the alarm.
The buzzer can be turned off by pressing the key
The visual alarm signal stays on until the temperature returns within the normal range.
LOW TEMPERATURE ALARM
If the room temperature is below the setpoint, the label [AL] and the temperature reached
alternate on the display. The buzzer sounds.
Press up to display the duration of the event causing the alarm.
The buzzer can be turned off by pressing the key
The visual alarm signal stays on until the temperature returns within the normal range.
HIGH AND LOW TEMPERATURE ALARMS MEMORIZED
The defrost led blinking at high frequency indicates high or low temperature alarm.
The temperature reached blinks on the display
The duration of the event causing the alarm, expressed in minutes, blinks on the display.