Sagi KUBA (внутренний агрегат) [30/116] User parameter configuration probe reading

Sagi KIABA (внутренний агрегат) [30/116] User parameter configuration probe reading
14
A6
temperature alarm exclusion time (only if A1 and/or A2 0)
15 min 15 min 0 240
A7
temp. alarm exclusion time after evap. stop (for A1 and/or A2 0)
60 min 60 min 0 240
EVAPORATOR FAN ADJUSTMENT
F1
temper. above which the evap. fan stops
(only if /A = 1 and F7 = 3 or 4)
-1°C -1°C -55 +99
F2
fan differential (relating to F1, only if /A = 1 and F7 = 3 or 4) +2°C +2°C 1 15
F3
evaporator fan func. during regular operation (0=OFF; 1=ON;
2=parallel with compressor; 3=determined by F1 and F2 with comp.
ON and OFF with comp. OFF
1 1 0 4
F4
evap. vent. operation during defrost and dripping (0= OFF, 1= ON,
2= determ. with F7)
0 0 0 2
F5
evaporator fan stop after dripping 3 min 3 min 0 15
F6
temperature below which the condenser fan turns off 20 °C 20 °C -55 +99
F7
evap. vent. operation during standard oper. (0= OFF, 1= ON, 2=
parallel with comp., 3= determined with F1 and F2, 4= determined
with F1 and F2 with comp. ON, OFF with comp. OFF)
+3°C +3°C 0 4
F8
condenser fan func. during regular operation (0=parallel with
compr.; 1=ON); also refer to F6 and F7
0 0 0 1
F9
condenser fan func. during defrost and dripping (0=OFF; 1=ON,
2=ON if Tc35°C and OFF if Tc<33°C)
0 0 0 2
FA
critical temperature for signalling high condensation temperature 55°C 55°C -55 +99
Fb
critical temperature for high pressure akarm 57°C 57°C -55 +99
PRINT
P0
Configuration parameters printing enable (0 = disabled) 1 1 0 1
P1
Sampling time (see also parameter P6) 30 min/ore 30 min/ore 1 60
P2
Selection of temperature probe to be printed (0 = none, 1=chamber
probe, 2 = chamber and evaporator probe, 3 = all)
1 1 0 3
P3
Payslip heading selection (0 =excluded, 1= Refrigerator,
2=Refrigerated counter)
2 2 0 2
P4
Equipment identification number printing enable (0 = no, 1= yes) 1 1 0 1
P5
Selection of language for payslip heading (1 = Italian, 2 = English,
3 = French, 4 = Spanish, 5 = German)
1 1 -1 5
P6
Selection of unit of measure for sampling time (1 = minutes, 2 =hours) 1 1 1 2
COMMUNICATIONS MANAGEMENT
L1
Instrument address (date detected in printing phase if P4 = 1) 1 1 0 256
L2
Serial port management (o = not utilised, 1 = print) 1 1 0 1
L3
Baud Rate data transmiss. (1=2400, 2=4800, 3=9600, 4=18200) 3 3 1 4
L4
Transmission control mode (0 = no parity, 1 = odd, 2 = even) 0 0 0 2
USER PARAMETER CONFIGURATION - PROBE READING
Press the on/sby/enter key over 5 secods (thus avoiding Sby) to gain access to probe reading
and user parameter list.
The display shows the first label “Pd
Use the up and down keys to scroll probe and parameter reading.
Press the on/sby/enter key to confirm your selection and enter the mode for reading probes or
changing parameters.
The current value blinks on the display.
Use the keys
to select the new value, applicable to parameters only.
Press the on/sby/enter key to exit or confirm the selection of the parameter new value; the
setting stops blinking.
You can leave the programming phase by waiting for 30 seconds without operating on the card, or pressing for 5 seconds.
In both cases, there you will hear 3 consecutive, short beeps and the display will temporarily show [ESC].