Emotron CDU/CDX 48-026 [38/82] Emotron dsv 5445 5444

Emotron CDU/CDX 48-026 [38/82] Emotron dsv 5445 5444
EMOTRON DSV 5445/5444
Page 38
Emotron 21.04.09
Adr. Parameter FU-Control Remarks TUDY/X TUDZ
F23 encoder factor setup P 256 8192
F24
switch to F23-default P
These cells are only for diagnostic purposes. 'F23' is
for '40 MHz' normally encoder pulses / 4, or for the '50
MHz' version encoder pulses 4. In the case of older
lift programs below '50 MHz', 'F23' = encoder pulses
per revolution. A new calculation can be performed
with parameter 'F24' = 1 in the event of 'parameter
error' after setting with help of 'FU-Control' (the 'error'
is then possibly corrected).
2 2
F25 show firmeware
P 0 = shows firmware-typ after 'reset' and 'b3<cr>;<cr>'
1 1
F26 stop distance to floor
P Stopping distance after level magnet/zone. This value
must be adjusted to the level values in the lift
controller.
Value range: 0 - 250 mm
65
40 for LISA
20
F29 A0-old=242 A0-new=3862
P Selection possible only in association with TUDYxxN,
TUDXxxN, TUDZxxN (with AUDYxxN or AUDZxxN
firmware, only 'F29' = '242' may be selected,
otherwise output 'A0' will not function). With devices
with MNo. 217000 and higher with command
programs after 22.05.2002, one can decide whether
'A0' only displays 'Controller running' as in the past, or
can be employed as a signal to switch the motor
contactors correctly ('F29' must be equal to '3862' in
this case). This ensures compatibility with several
competitors).
3862
242
Schmitt +
Sohn,
Findili
3862
F30 PWM Adjustment fine P
This value may not be changed without
consultation with the factory.
The PWM is already matched to the motors. SM225
winches run, for example with 15 kHz (F30 = 85).-
Very large asynchronous gearless sometimes only
with 2.5 kHz, since an internal jumper furthermore
controls the range 10 kHz - 20 kHz, a readjustment of
the 'F30' parameter can possibly lead to unexpected
results and damage to the drive or converter caused
by overheating.
124 124
F31 Number of poles
P Rating plate or manufacturer's specification.
(F31=120 x f
n
/n
n
, round the calculated number to the
next even whole number)Value range: 2 – 128.
4...8
8...128
I I-part run (normal)
P I-gain in speed controller during normal running; the
higher the value, the smoother the running. Start
value = '40'. Please take note that this parameter is
used only with the basic programs for 'normal' geared
systems (e.g. with LIFT7SZ.KOM), while all other
programs, especially those for '50 MHz', use the value
for constant run from the variable '0E1E'! The
programs for high quality drives exchange the
parameter 'I' during starting with '0E1C' and during
the run with '0E1E' and switch back to '0E1C' only
with the threshold '0E12'. This 'adaptive switchover of
the I-gains' is needed only to perform the 'virtual load
measurement'.
8 40
K P-part speed run
P P-gain in the speed controller during normal running.
Start value: see F7, value range: 50 – 4000 possible
600 200
t Rotor time constant
P See lift instructions (explanation of parameters). Old
motors between 40 and 250, in new systems
125 … 600, value range: 25 – 1000, start value is
'250' for 'TUDY/X' or '600' for 'TUDZ' with new motors.
The start value is '50' for old motors (only '40 MHz').
275
(50 is
recommend
ed for old
motors)
600
(the
value
moves
from
300-900)