Daikin EUW10KZW [14/49] Capacity tables

Daikin EUW10KZW [14/49] Capacity tables
LEAVING WATER
CONDENSER
40 45 50 55
LWE
MODEL
CC HC PI CC HC PI CC HC PI CC HC PI
-10 5 5.7 9.5 3.84 5.0 9.2 4.20 - - - - - -
8 9.8 15.4 5.69 8.7 14.9 6.31 - - - - - -
10 14.3 22.4 8.22 12.9 22.0 9.18 - - - - - -
12 18.2 27.4 9.37 16.3 26.7 10.53 - - - - - -
16 19.5 31.1 11.79 17.3 30.2 13.04 - - - - - -
20 28.6 45.2 16.93 25.9 44.5 18.85 - - - - - -
24 36.5 55.0 18.83 32.5 53.3 21.2 - - - - - -
32 39 62 23.6 35 60 26.1 - - - - - -
36 48 76 28.7 43 75 31.9 - - - - - -
40 57 90 33.9 52 89 37.7 - - - - - -
44 65 100 35.8 58 98 40.0 - - - - - -
48 73 110 37.7 65 107 42.3 - - - - - -
52 68 107 40.5 60 104 44.9 - - - - - -
56 77 122 45.7 69 119 50.7 - - - - - -
60 86 136 50.8 78 133 56.5 - - - - - -
64 94 145 52.7 84 142 58.9 - - - - - -
68 102 155 54.6 91 151 61.2 - - - - - -
72 109 165 56.5 98 160 63.5 - - - - - -
-5 5 7.6 11.5 3.89 6.9 11.2 4.27 6.2 10.8 4.65 - - -
8 12.9 18.8 6.00 11.8 18.4 6.65 10.5 17.8 7.34 - - -
10 18.1 26.3 8.35 16.8 26.0 9.30 15.4 25.6 10.35 - - -
12 22.0 31.4 9.54 20.2 30.8 10.72 18.0 29.7 11.90 - - -
16 25.7 38.0 12.41 23.5 37.1 13.71 20.9 35.9 15.10 - - -
20 36.3 53.2 17.19 33.7 52.5 19.09 30.8 51.7 21.2 - - -
24 44.1 62.8 19.18 40.5 61.6 21.5 36.0 59.4 23.9 - - -
32 51 76 24.8 47 74 27.4 42 72 30.2 - - -
36 62 91 29.6 57 90 32.8 52 88 36.3 - - -
40 73 106 34.4 67 105 38.2 62 103 42.4 - - -
44 80 116 36.4 74 114 40.6 67 111 45.1 - - -
48 88 126 38.4 81 123 43.1 72 119 47.8 - - -
52 88 129 42.0 81 127 46.5 73 123 51.4 - - -
56 98 144 46.8 91 142 51.9 83 139 57.5 - - -
60 109 159 51.6 101 157 57.3 92 155 63.5 - - -
64 117 169 53.6 108 167 59.7 98 163 66.3 - - -
68 124 179 55.5 115 176 62.2 103 171 69.0 - - -
72 132 189 57.5 121 185 64.6 108 178 71.7 - - -
0 5 9.7 13.6 3.98 8.9 13.2 4.37 8.1 12.9 4.77 7.3 12.5 5.26
8 15.8 22.0 6.26 14.7 21.5 6.95 13.4 21.0 7.70 12.1 20.5 8.50
10 21.9 30.1 8.35 20.6 29.7 9.27 19.2 29.4 10.29 17.2 28.5 11.40
12 25.7 35.2 9.65 24.1 34.8 10.91 22.0 33.8 11.89 19.5 32.7 13.29
16 31.5 44.3 12.94 29.2 43.4 14.31 26.7 42.3 15.81 24.1 41.4 17.42
20 43.8 60.6 17.18 41.3 60.0 19.03 38.5 59.2 21.1 34.4 57.4 23.3
24 51.5 70.4 19.39 48.2 69.6 21.9 44.1 67.4 23.9 39.0 65.2 26.7
32 63 89 25.9 58 87 28.6 53 85 31.6 48 83 34.8
36 75 105 30.1 71 103 33.3 65 102 36.9 59 99 40.7
40 88 121 34.4 83 120 38.1 77 118 42.1 69 115 46.6
44 95 131 36.6 90 130 40.9 83 127 45.0 73 123 50.0
48 103 141 38.8 96 139 43.8 88 135 47.8 78 130 53.4
52 107 149 43.1 100 147 47.7 92 144 52.7 83 140 58.1
56 119 166 47.3 112 163 52.4 104 161 57.9 93 156 64.0
60 132 182 51.5 124 180 57.1 116 178 63.2 103 172 69.9
64 139 192 53.8 131 190 60.0 121 186 66.0 108 180 73.3
68 147 201 56.0 138 199 62.8 127 194 68.8 112 188 76.7
72 154 211 58.2 145 209 65.7 132 202 71.6 117 195 80.0
4TW53472-1D 4TW53472-2B
4TW53472-3B 4TW53472-4B
SYMBOLS
CC : Cooling capacity (kW)
HC : Heating capacity (kW)
PI : Power input (kW)
LWE : Leaving Water Evaporator (°C)
NOTES
1 Cooling capacity (CC)
CAP = Cooling capacity from table (kW)
Capacity is for chilled water range Dt = 25°C
2 Power input (PI)
PI = Power input from table (kW)
Power input is total input kW: compressor + control circuit + pumps (kW)
3 Water flow rate (WFR)
WFR = (860 x CC)/(60 x Dt) (l/min)
CC = From above calculation
Dt = Chilled water temperature rise within 2-5°C
WFR should always be within the limits
4 No pumps are supplied with the unit, so the added power input for the pumps is
calculated as (WFR m
3
/s x DPa) m
3
/s /0.3 as fixed by 6/C/003 (Dp = pressure drop
from pressure drop curves).
This is for cooled and cooling water.
Water-cooled R-407C EUW5-24KZW
4
Capacity tables
4-1
Cooling / heating capacities
1
4
4-1
12
Applied Systems Chillers