Daikin EUW10KZW [9/49] Specifications

Daikin EUW10KZW [9/49] Specifications
NOMINAL CAPACITY, CAPACITY STEPS and NOMINAL INPUT
UNITS 44hp 48hp 52hp 56hp
NOMINAL CAPACITY Cooling kW 121 130 142 155
CAPACITY STEPS 4466
NOMINAL INPUT Cooling kW 34.3 36.6 40.2 44.1
EER 3.59 3.55 3.53 3.51
TECHNICAL SPECIFICATIONS
UNITS 44hp 48hp 52hp 56hp
DIMENSIONS Unit H mm 1,200 1,800
W mm 600 600
D mm 1,200 1,200
WEIGHT Machine weight kg 654 668 920 940
MATERIAL Polyester painted steel plate
COLOUR Ivory white / Munsell code 5Y7.5/1
SOUND LEVEL Sound pressure dBA −−−−
Sound power dBA 75 77 73 73
EVAPORATOR Type Brased plate heat exchanger
Qty 2233
Minimum water volume in the system l 311 311 205 205
Nominal water flow l/min 347 373 407 444
Water flow range (min/max) l/min 173/694 186/745 204/814 222/889
Insulation material Polyethylene foam
CONDENSER Type Brased plate heat exchanger
Qty 2233
Nominal water flow l/min 442 474 519 567
Water flow range (min/max) l/min 221/883 237/948 260/1,038 283/1,133
REFRIGERANT CIRCUIT Refrigerant type R-407C
Refrigerant charge kg 10.2 11.2 13.8 13.8
No. of circuits 4466
Refrigerant control Thermostatic expansion valve
COMPRESSOR Type Hermetically sealed scroll
Qty x model 2xJT300DA-YE
2xJT335DA-YE
4xJT335DA-YE 4xJT212DA-YE
2xJT300DA-YE
2xJT212DA-YE
4xJT300DA-YE
No. of compressors 4466
Speed rpm 2,900 2,900 2,900 2,900
Refrigerant oil type FVC68D
Refrigerant oil charge l 4 x 2.7 4 x 2.7 6 x 2.7 6 x 2.7
PIPING CONNECTIONS Evap. water in/outlet mm 2x2xFBSP 38 3x2xFBSP 38
Condenser water in/outlet mm 2x2xFBSP 38 3x2xFBSP 38
Evaporator water drain Field installation
Relief device outlet Field installation
Filter strainer Field installation
Flow switch Field installation
SAFETY DEVICES High pressure switch / Low pressure switch / Freeze-up protection / Reverse phase protector / Discharge temperature protection /
Compressor motor overcurrent / Anti recycling timer / Guard timer
Water-cooled R-407C EUW5-24KZW
3
Specifications
1
3
7
Applied Systems Chillers