Daikin EUW10KZW [19/49] Cooling capacities with glycol

Daikin EUW10KZW [19/49] Cooling capacities with glycol
4
Capacity tables
4-2
Cooling capacities with glycol
4TW54179-1
CORRECTION FACTOR FOR GLYCOL
Ethylene glycol
Propylene glycol
Legend
Kc Correction on cooling capacity
Ki Correction on power input
Kf Correction on flow rate
Kp Correction on pressure drop
% Glycol
Required glycol concentration
Type Concentration (wt%) 0 10 20 30 40
Ethylene glycol
Freezing point °C 0 -4 -9 -16 -23
Minimum LWE °C 4 2 0 -5 -11
Propylene glycol
Freezing point °C 0 -3 -7 -13 -22
Minimum LWE °C 4 3 -2 -4 -10