106 Function
4.2 Low Pressure Protection Control
This low pressure protection control is used to protect compressors against the transient
decrease of low pressure.
In the case of multi-outdoor-unit system, the entire system performs this control in the
following sequence.
Low pressure not limited
Pe<0.34MPa
Low pressure standby
Low pressure limited
All STD compressors
stop.
Master unit:52 Hz + OFF + OFF
Slave unit:Stop
Pe<0.25MPa
Pe<0.15MPa Pe>0.30MPa
Pe>0.39MPa
Pe<0.07MPa
Pe: LP pressure sensor detection
value for master unit
When occurring 4 times within 30 min.,
the malfunction code E4 is output.
Hot gas SVP = OFF
Hot gas SVP = ON